This page puts the parameters of the racks and of the containment together, each row with its basis. What this site gives is the prevailing range of this category and the standards it sits in; the specific values are confirmed item by item on the quotation drawings.

1 · Rack parameters

The prevailing specification range and the standards of this class of rack. The specific values of this site's products are confirmed item by item on the quotation drawings.
Item Value Basis
Mounting width 19 in (482.6 mm), EIA hole spacing EIA/ECA-310-E
Frame width 600 mm / 700 mm / 800 mm Standard data sheets
Height options 42U / 45U / 48U / 52U Standard data sheets
Depth 1,000 mm / 1,200 mm, extendable to 1,372 mm (54 in) Standard data sheets
Static load capacity 1,360 kg (3,000 lb); heavy-duty 2,268 kg (5,000 lb) UL 2416 rated
Rolling load 1,588 kg (3,500 lb) Standard data sheets
Body sheet thickness Frame 14 gauge steel · doors and side panels 16 gauge steel · reinforcing corner brackets 12 gauge steel Standard data sheets
Front door perforation 79% Standard data sheets
Surface finish Pre-treatment + powder coating, 500 h salt spray ASTM B117 / D610-01
Open rack (optional) 21 in / OpenU 48 mm pitch / 48 V busbar OCP Open Rack V3
Empty cabinet weight 42U ≈ 184–248 kg; 48U ≈ 191–264 kg Standard data sheets

2 · Containment parameters

2 · Containment parameters
Item Value Basis
Aisle width 1,000 / 1,200 / 1,800 mm Standard data sheets
Compatible rack width 600 / 700 / 800 mm Standard data sheets
Compatible rack height 42U–48U (with and without base) Standard data sheets
End door height 90 in / 96 in Standard data sheets
Ceiling panel height 60 mm / 200 mm Standard data sheets
Ceiling interlock Solenoid lock 12 VDC / 200 mA, can connect to FDAS / BMS Standard data sheets
Panel flame retardancy UL 94 V-0 / ASTM E 84 / FM4910 (one of) Standard data sheets
Ceiling light transmission ASTM D1003 > 82% (transparent type) Standard data sheets
Salt spray 500 h, ASTM B117 / D610-01 Standard data sheets
Per-rack capacity up to 20 kW/rack after containment Standard data sheets

3 · Standards

3 · Standards
Standard What it governs
EIA/ECA-310-E Hole positions and mounting for 19 in racks
IEC 60297 19 in mechanical structure series standard
UL 2416 Rack load rating
UL 62368-1 Safety of audio/video and information technology equipment
UL 94 V-0 / ASTM E 84 / FM4910 Flame-retardancy rating of containment panels
ASTM B117 / D610-01 Salt spray corrosion
RoHS / CE Hazardous substance restriction / EU market access
OCP Open Rack V3 Open rack: 21 in / OpenU 48 mm / 48 V busbar

4 · Four things to ask when selecting

  1. 01 Device depth and weight Determines the depth and whether a heavy-duty model is needed
  2. 02 How wide the aisle must be Determines which tier the containment is calculated from
  3. 03 Whether the ceiling needs interlocking Determines whether the ceiling is a plain panel or an interlocked panel with a solenoid lock